HY5WS-17/50、HY5WS-12.7/50、HY5WS-16.5/50配电型避雷器
HY5WS-17/50配电型避雷器用于保护相应电压等级的电力变压器、开关柜、箱式变电站、电力电缆出线头、柱上油开关等配电设备免受大气和操作过电压的损坏。
常用避雷器型号: HY1.5W-0.28/1.3;HY1.5W-0.5/2.6;HY5WS-5/17;HY5WS-12.7/30;HY5WS-7.6/30;HY5WS-12.7/50;HY5WS-16.5/50;HY5WS-17/50;HY5WZ-3.8/13.5;HY5WZ-10/27;HY5WZ-12.7/45;HY5WZ-17/45;HY5WZ-51/134;HY2.5WD-8/19; HY2.5WD-13/31;HY5WD-12.7/31;HY5WD-19/45;HY5WD-20/45;HY5WR-7.6/27;HY5WR-10/27;HY5WR-17/45;HY5WR-51/134;放电计数JS-8,JSY-10;在线监测器JCQ-C;TBP-A-7.6F/85;TBP-B-7.6F/85;TBP-C-7.6F/85;TBP-A-7.6F/131;TBP-B-7.6F/131;TBP-C-7.6F/131;TBP-A(B、C)-7.6F/280W2;TBP-A-12.7F/85;TBP-B-12.7F/85;TBP-C-12.7F/85;TBP-A-12.7F/131;TBP-B-12.7F/131;TBP-C-12.7F/131;TBP-A(B、C)-12.7F/280W2
氧化锌避雷器主要产品电气性能参数:
类别
|
避雷器型号
|
避雷器额定电压(kV)
|
系统标称电压(kV)
|
持续运行电压(kV)
|
直流1mA参考电压(不小于)(kV)
|
0.75倍直流参考电压下漏流(不大于)(μA)
|
陡坡冲击电流(不大于)(kV)
|
雷电冲击电流(不大于)(kV)
|
操作冲击残压(不大于)(kV)
|
2mS方波通流容量(电流A、18次)
|
4/10μS冲击电流(kV)
|
低压
|
H(Y)1.5W-0.28/1.30
|
0.28
|
0.22
|
0.24
|
0.60
|
30
|
-
|
1.30
|
-
|
75
|
25
|
H(Y)1.5W-0.5/2.60
|
0.50
|
0.38
|
0.42
|
1.20
|
30
|
-
|
2.60
|
-
|
75
|
25
|
|
配电(S)
|
H(Y)5WS-5/15
|
5
|
3
|
4.0
|
7.5
|
30
|
17.3
|
15.0
|
12.8
|
100
|
65
|
H(Y)5WS-10/30
|
10
|
6
|
8.0
|
16.0
|
30
|
34.6
|
30.0
|
25.6
|
100
|
65
|
|
H(Y)5WS-17/50
|
17
|
10
|
13.6
|
25.0
|
30
|
57.5
|
50.0
|
42.5
|
100
|
65
|
|
电站(Z)
|
H(Y)5WZ-5/13.5
|
5
|
3
|
4.0
|
7.2
|
30
|
15.5
|
13.5
|
11.5
|
150
|
65
|
H(Y)5WZ-10/27
|
10
|
6
|
8.0
|
14.4
|
30
|
31.0
|
27.0
|
23.0
|
150
|
65
|
|
H(Y)5WZ-17/45
|
17
|
10
|
13.6
|
24.0
|
30
|
51.8
|
45.0
|
38.3
|
150
|
65
|
|
H(Y)5WZ-51/134(130,125)
|
51
|
35
|
40.8
|
73.0
|
40
|
154(150,154)
|
134(130,125)
|
114(112,110)
|
400
|
65 100
|
|
H(Y)5WZ-52.7/134(130,125)
|
52.7
|
35
|
42.2
|
73.0
|
40
|
400
|
|||||
H(Y)5WZ-54/134(130,125)
|
54
|
35
|
43.2
|
74.0
|
40
|
400
|
|||||
H(Y)10WZ-100/260
|
100
|
110
|
80
|
145
|
50
|
299
|
260
|
221
|
600
|
100
|
|
H(Y)10WZ-102/265
|
102
|
110
|
81.6
|
148
|
50
|
305
|
265
|
226
|
600
|
100
|
|
H(Y)10WZ-108/281
|
108
|
110
|
86.4
|
157
|
50
|
332
|
281
|
239
|
600
|
100
|
|
发电机(D)
|
H(Y)5WD-4/9.5
|
*4
|
3.15
|
3.2
|
57
|
40
|
10.7
|
9.5
|
7.6
|
400
|
65
|
H(Y)5WD-8/18.7
|
*8
|
6.3
|
6.3
|
11.2
|
40
|
21.0
|
18.7
|
15.0
|
400
|
65
|
|
H(Y)5WD-13/31
|
*13.5
|
10.5
|
10.5
|
18.6
|
40
|
34.7
|
31.0
|
25.0
|
400
|
65
|
|
H(Y)5WD-17.5/10
|
*17.5
|
13.8
|
13.8
|
24.4
|
40
|
44.8
|
40.0
|
32.0
|
400
|
65
|
|
H(Y)5WD-20/45
|
*20
|
15.8
|
15.8
|
28.0
|
40
|
50.4
|
45.0
|
36.0
|
400
|
65
|
|
H(Y)5WD-23/51
|
*23
|
18.0
|
18.0
|
31.9
|
40
|
57.2
|
51.0
|
40.8
|
400
|
65
|
|
H(Y)5WD-25/56.2
|
*25
|
20.0
|
20.0
|
35.4
|
40
|
62.9
|
56.2
|
45.0
|
400
|
65
|
|
旋转电机(D)
|
H(Y)2.5WD-4/9.5
|
*4
|
31.5
|
3.2
|
5.7
|
30
|
10.7
|
9.5
|
7.6
|
200
|
65
|
H(Y)2.5WD-8/18.7
|
*8
|
6.3
|
6.3
|
11.2
|
30
|
21.0
|
18.7
|
15.0
|
200
|
65
|
|
H(Y)2.5WD-13.5/31
|
*13.5
|
10.5
|
10.5
|
18.6
|
30
|
34.7
|
31.0
|
25.0
|
200
|
65
|
|
并联补偿电容器(R)
|
H(Y)5WR-8/13.5
|
5
|
3
|
4.0
|
7.2
|
40
|
-
|
13.5
|
10.5
|
400
|
65
65-100
|
H(Y)5WR-10/27
|
10
|
6
|
8.0
|
14.4
|
40
|
27.0
|
21.0
|
400
|
|||
H(Y)5WR-17/44
|
17
|
10
|
13.6
|
24.0
|
50
|
46.0
|
35.0
|
400-1200
|
|||
H(Y)5WR-48/134(130,125)
|
48
|
35
|
38.1
|
73.0
|
50
|
-
|
134(130,125)
|
105
|
400-1200
|
65-100
|
|
H(Y)5WR-51/134(130,125)
|
51
|
35
|
40.8
|
73.0
|
50
|
105
|
400-1200
|
65-100
|
|||
H(Y)5WR-52.7/134(130,125)
|
52.7
|
35
|
42.2
|
73.0
|
50
|
105
|
400-1200
|
65-100
|
|||
H(Y)5WR-54/134(130,125)
|
54
|
35
|
43.2
|
73.0
|
50
|
105
|
400-1200
|
65-100
|
|||
变压器中性点
|
H(Y)1.5W-55/132
|
55
|
110
|
44
|
79
|
40
|
-
|
132
|
126
|
400
|
65
|
H(Y)1.5W-60/144
|
60
|
110
|
48
|
85
|
40
|
144
|
135
|
400
|
65
|
||
H(Y)1.5W-72/186
|
72
|
110
|
58
|
103
|
40
|
186
|
174
|
400
|
65
|
||
H(Y)1.5W-73/200
|
73
|
110
|
58.4
|
105
|
40
|
200
|
165
|
400
|
65
|
||
电气化铁道(T)
|
H(Y)5WT-42/120
|
42
|
27.5
|
34
|
65
|
40
|
138
|
120
|
98
|
400
|
65
|
H(Y)5WT-84/240
|
84
|
55
|
68
|
130
|
40
|
276
|
240
|
196
|
400
|
65
|
|
H(Y)10WT-42/120
|
42
|
27.5
|
34
|
65
|
40
|
138
|
120
|
98
|
400
|
65
|
|
H(Y)10WT-84/240
|
84
|
55
|
68
|
130
|
40
|
276
|
240
|
196
|
400
|
65
|
|
线路(X)
|
H(Y)10WX-17/60
|
17
|
10
|
13.6
|
25
|
40
|
70
|
60
|
-
|
400
|
65
|
H(Y)10WX-51/220
|
51
|
35
|
40.8
|
73
|
40
|
240
|
220
|
-
|
400
|
65
|
|
H(Y)10WX-51/170
|
51
|
35
|
40.8
|
73
|
40
|
190
|
120
|
-
|
400
|
65
|
注:1、H(Y)表示可提供瓷外套式与复合外套式。 2、*此为电机的额定电压。